Suchen Sie etwas anderes?
Scenario details:
- We want to switch a relay based on the sunrise and sunset to activate a lighting system
- It is not possible to set a fixed time, as the time for sunrise/sunset depends on the location (sunrise/ sunset does not happen at the same time in Madrid than it does in Barcelona or Mexico DF) and on the time of year (sunrise/ sunset does not happen at the same time in Summer as it does in Winter). To do so, the modem MTX must be set up as an astronomical clock
- We also want the lights to connect 30 minutes prior to sunset and disconnect 30 minutes after sunrise
- The device location is the town of Cardedeu, with the GPS latitude: 41.6333 and longitude: 2.36667
Solution: MTX-Tunnel firmware + MTX-Java-IoT
EXAMPLE of settings (file config.txt) for such scenario:
Configuration | Observations |
MTX_pin: 0000 MTX_model: 199802407 MTX_mode: none MTX_TPProtocol: ntp MTX_TPServer: ntp.roa.es MTX_TPServer2: es.pool.ntp.org MTX_latitude: 41.6333 MTX_longtude: 2.36667 SMS_allPhones: on SMS_ATEnabled: on SMS_ATResponse: on SMS_sendIP: on GPRS_apn: movistar.es GPRS_login: MOVISTAR GPRS_password: MOVISTAR GPRS_timeout: 1 OUTPUT_mode1: astronomical OUTPUT_config1: -30;30 |
SIM Card PIN MTX model We do not want GPRS Time synch. protocol Time server (the MTX must sync the time) Backup time server GPS latitude GPS longitude All phones are allowed IP by SMS authorized AT by SMS allowed SMS AT responses activated APN GPRS provided by the GSM operator GPRS login provided by the GSM operator GPRS password provided by the GSM operator The modem will not be permanently connected OUTPUT 1 (relay 1) in function of Sun Offset -30 minutes and 30 min |
Details:
- This scenario can also be combined with others that make simultaneous Serial/GPRS gateways to access serial devices (modbus or others), as well as others where MTX-Tunnel independently collects modbus records and sends them via JSON to a Web platform
- As of the MTX-Tunnel v11.12 version, it is possible to use the command AT ^ MTXTUNNEL = SETIOMAINTENANCE, idGPIO, mode to establish a maintenance mode (mode = 1) in a specific output GPIO. When an output is in maintenance mode, the output does not obey the astronomical clock, but is managed by the command AT ^ MTXTUNNEL = SETIO, idGPIO, value